Page 121 - JCAU-6-4
P. 121

Journal of Chinese
            Architecture and Urbanism                      Indoor wind environment in buildings for Qinghai-Tibet plateau of China




            Table 2. 48‑h indoor temperature change at Dege Scripture Printing House (July 2022)
            Floor    Testing location     Average temperature (°C)  Max (°C)  Min (°C)  Temperature change value (°C)
            /        Outdoor              17                     11.6       23.9        12.3
            1F       Hall of Worship      15.5                   13.6       19.2        5.6
            2F       East District Sutra Hall  16.7              15.1       18.8        3.7
            2F       West District Sutra Hall  16.9              16.4       18          1.6

            showing warmer temperatures. Temperature variation   ensure a smooth transition between smaller and larger
            within the same floor ranged from 1°C to 5.6°C, with   grid sizes. In key observation areas, such as sidewalks, the
            overall indoor temperatures being relatively stable.  total thickness of the boundary layer is set to be close to
                                                               pedestrian height, with more than five grid layers assigned
              During the investigation of the wind environment
            at DSPH, it was found that airflow could be clearly felt   (Li, 2010). The Architectural Institute of Japan, based on
                                                               numerous simulation experiments, recommends modeling
            indoors. Traditional Tibetan buildings on the Tibetan   the target building in detail in the 1 – 2 H zone (where H
            plateau typically have limited or partially open windows   represents the characteristic height, typically the height of
            on the north side to improve airtightness and reduce heat   the tallest building in the area), while the computational
            dissipation, allowing them to better adapt to the local alpine   domain should cover 2 – 3 H. This approach leads to more
            climate. To  minimize  the  effects  of  solar radiation and   accurate results (Hou, 2023).
            harsh weather (Li et al., 2014), these buildings are usually
            constructed with thick walls and few windows, resulting   The number  of  computational grids is an important
            in relatively poor indoor ventilation. The distinctive   factor that affects the accuracy of the simulation results.
            ventilation of DSPH is closely tied to its natural ventilation   Grid division in PHOENICS is accomplished using the
            system, which embodies the wisdom of passive building   software’s PARSOL processing method. After multiple
            design. However, there are areas where improvements   adjustments, it was ensured that variations in the number
            can be made. Across software simulation, this study   of selected grids did not significantly affect the simulation
            summarized the notable characteristics of the indoor wind   results. The grid resolution was set to meet the required
            environment at  DSPH, offering insights  into optimizing   calculation standard of 20 cm × 20 cm. Ultimately, the total
            passive building design for traditional buildings in the   number of grids used in the simulation was determined
            Tibetan plateau.                                   to be 1 million. The ground roughness coefficient of the
                                                               DSPH area was calculated, and the DSPH was categorized
              The measured average wind speed in the main indoor   as Class  B. For the simulation, a ground roughness
            space of DSPH was 0.30  m/s, which falls within the   coefficient value of 0.16 was used (Table 3).
            comfortable  range for  human  occupation. The  2   and
                                                     nd
            3  floors, where wooden carving boards of scripture are   3.4. PHOENICS parameter settings
             rd
            primarily stored, exhibited good ventilation and dry   3.4.1. Calculation of domain and boundary conditions
            air. However, certain areas on the 1  floor lacked proper
                                         st
            ventilation, resulting in poor indoor air quality and   Using 3D scanning and field measurements, accurate STL
            discomfort.                                        3D models were created for use in the Phoenics wind
                                                               environment simulations. Irrelevant  factors affecting
            3.3. Wind environment simulation analysis of DSPH  indoor airflow were simplified in this model. The model
                                                               dimensions are 46.9 m × 26.2 m × 15.9 m, and the length
            In this simulation, the realizable k-ɛ model is used to   and width of the building were multiplied by 10, while
            analyze the flow field, considering the dominant southeast   the height was multiplied by 5, resulting in a calculation
            wind direction and the average wind speed of 1.5  m/s   domain of 469 m × 262m × 79.5m.
            throughout the year in Dege as the initial condition. The
            reproduction domain of the model is formed by extending   Since frictional forces from natural wind increase
            the target domain within a specific range. To ensure   closer to the ground, causing wind speeds to decrease, it is
            accuracy in the simulation, the grid size for the target   necessary to account for the variation of natural wind with
            domain in the small-scale building wind environment   height in the calculations (Taylor, 1915):
            simulation is kept below 2.0 m, and the grid size of the      h  α
                                                                 =
            computational domain is kept below 5.0 m. At the same   vv 1                                 (I)
            time, one or more transition zones are established to     h 1 


            Volume 6 Issue 4 (2024)                         7                        https://doi.org/10.36922/jcau.2396
   116   117   118   119   120   121   122   123   124   125   126