Page 65 - JCAU-5-2
P. 65

Journal of Chinese
            Architecture and Urbanism                                                Cooling energy-saving mechanism



            envelope with different performance is roughly the same.
            Its distribution trend is composed of two parts. The first
            part is the time when the outdoor dry bulb temperature
            is between 26°C and 27°C (831 h). The behavioral energy-
            saving effect brought by increasing temperature set-point
            makes the hourly load reduction rate of these scatter
            points all 100%, and the scatter points are distributed in
            parallel. The other part is that when the outdoor dry bulb
            temperature is higher than 27°C (2510 h), the hourly load
            reduction rate decreases rapidly with the increase of air
            conditioning load in an exponential curve, most of which
            are concentrated below 20% level and form a smooth
            curve. (ii) Although the hourly load reduction rate (100%)
            of scattered points in the first part is higher than that of
            scattered points in the second part, the latter has more   Figure 9. Comparison of hourly load reduction rate based on hourly load
            corresponding moments and a larger load base before   variation. Source: Graph by the authors
            set-point rise, which plays a controlling role in the change
            trend of macro energy-saving rate. (iii) For the second part
            of scattered points, the cooling load demand range narrow
            results in the bigger curvature of the hourly load reduction
            rate curve (that is, the more concave to the origin), that is,
            the load reduction rate is smaller. From this microscopic
            distribution feature, the rule above can be proven that the
            monthly and annual absolute energy-saving and relative
            energy-saving rates decrease with the improvement of the
            thermal performance of the envelope.

            5. Discussion
            As mentioned above, when studying the energy-saving   Figure 10. Comparison of annual energy savings before and after adding
                                                               internal heat source. Source: Graph by the authors
            effect of 1°C increase in the temperature set-point of air-
            conditioning under different thermal performance of outer   rises by 1°C. It can be found that after considering the
            envelope of office buildings of the same size to better reveal   influencing factors of internal heat source, the annual
            the difference in the influence of a single variable of the   cooling consumption of the four grades of envelope
            set-point on the energy-saving effect, this paper disregards   structures increases significantly before the set-point rise,
            the influences of personnel, lighting, equipment, and other   but the annual energy saving rate does not change much.
            internal heat sources. However, in fact, the office building   The energy-saving rate of top-grade and lower-grade
            internal heat source is large, which will greatly increase the   envelope is slightly higher than that without internal heat
            building cooling consumption, so that the energy-saving   source. The reason is that although the addition of internal
            effect will change. In this section, the simulation results   heat source will increase the demand for cooling load of
            after considering the internal heat source are compared   the building, the building is still in the same city with the
            with the previous analysis. In the simulation, it is assumed   same climatic conditions. After the addition of internal
            that the office building can accommodate 35 office workers,   heat source, the number of hours of air-conditioning is
            the human load index is 136  W/person, the clustering   almost unchanged, and the energy-saving mechanism has
                                                      2
            coefficient is 0.96, the lighting load index is 11 W/m , the   not fundamentally changed. Figure 10 shows the annual
            lighting couse coefficient during office hours is 0.6, the   absolute  energy  savings  and energy saving increment
            equipment load index is 20  W/m , and the equipment   comparison of the four grades of envelope before and
                                        2
            couse coefficient during office hours is 0.8.      after  considering  the  internal  heat  source  as  well.  It  is
              Figure  10 shows the comparative diagram of annual   not difficult to find that the annual energy-saving rate is
            energy-saving rate and annual cooling consumption   basically the same after adding the internal heat source,
            before and after the addition of internal heat source in   while the annual cooling consumption increases. Therefore,
            office buildings under the condition of four grades of   when there is an internal heat source, the absolute energy
            envelope when the temperature setpoint of air conditioner   saving of the four grades of envelope increases to a similar


            Volume 5 Issue 2 (2023)                         11                       https://doi.org/10.36922/jcau.0877
   60   61   62   63   64   65   66   67   68   69   70