Page 49 - IJAMD-2-1
P. 49

International Journal of AI for
            Materials and Design
                                                                                     ML-based MPC for multizone BAC


              When the test space is controlled by the existing building   The ML model for predicting indoor PMV is developed
            management  system (referred  to as  “BMS”  in  this  study),   using a NARX feedback neural network, a recurrent
            cooling power delivered to the test space is regulated by   neural network commonly used for time-series modeling.
            controlling the chilled water flow rate through each FCU’s   A  detailed  description of the  development of  the  ML
            cooling coil through a motorized water valve using a PID   network for MPC is provided in Section 4. For the MPC
            controller. The control is based on a temperature setpoint of   controller, the cooling power supplied by the FCU cooling
            21°C, measured by a thermostat located at the diffuser outlet.  coil serves as the manipulated variable and is the control
              Each zone is equipped with a set of sensors, including   signal  to  be  optimized.  The  current  cooling  power  is
            globe temperature, ambient temperature, and humidity   measured as feedback using the BTU meter installed in
            sensors for measuring thermal comfort, as well as CO    each FCU within the zone. The number of occupants,
                                                          2
            sensors for measuring occupancy within each zone. For   representing the internal heat load, is measured using the
            the evaluation of the predicted mean vote (PMV) as per   duct CO  and flow sensors at the FCU and PAU, along with
                                                                      2
            ASHRAE 55,  ambient air velocity, metabolic rate, and   the indoor CO  sensors in each zone. Outdoor temperature
                       33
                                                                          2
            clothing insulation factor for each occupant were assumed   and solar radiation data are obtained from the rooftop
            constant  at  0.1  m/s,  1.2  met,  and  0.5  CLO,  respectively.   weather station. The solar heat gain from the windows
            Duct  air  temperature,  humidity,  and  flow  sensors  were   (Q ) is derived as a function of solar radiation, as shown
                                                                 win
            installed at both the supply and return sides of the PAUs   in Equation I. This equation accounts for heat gain from
            and FCUs to enable precise measurement of the cooling   both the shaded (by blinds) and unshaded regions of the
            capacity of supply air for each zone. In addition, duct CO    window. Here, SR represents the ratio of the area shaded
                                                          2
            sensors were installed on both the supply and return sides   by blinds to the total window area, A  is the total window
                                                                                            win
            of FCUs. By integrating data from the duct CO  and flow   area, E  is the incident solar radiation, SHGC is the solar
                                                  2
                                                                    inc
            sensors in the FCUs and PAUs with the indoor CO  sensors   heat gain coefficient, and  IAC is the indoor attenuation
                                                   2
            in each zone, the occupancy of each zone was determined.  coefficient for blinds, which are made of light translucent
              A weather station, equipped with outdoor temperature,   fabric. The SHGC values of the windows used in the study
            humidity, and solar radiation sensors, was installed on the   are obtained from the as-built drawings of the test building.
            rooftop of the building. The specifications of these sensors,   For a given window type and climate, SHGC is generally
                                                                                           34
            installed in the test space, are summarized in Table 1.  considered a constant parameter  and is commonly
                                                               used in evaluating building energy performance.  As per
                                                                                                      35
            3. MPC controller for ACMV                         the ASHRAE Handbook,  SHGC and  IAC are assumed
                                                               constant, with values of 0.287 and 0.75 (for the shaded
            The MPC controller comprises an ML-based building   region), respectively. 33
            dynamics  predictive model and  an optimization  solver.
                                                                    SR A win  * E inc  1  SR * A win
                                                                       *
            Table 1. Specifications of the sensors installed in the test space  Q win   * SHGC IAC   *E  * SHGC  (I)
                                                                           *

                                                                             inc

            Location     Sensors      Range     Accuracy            region shaded by blinds  unshaded region
            Outdoor  Air temperature  −40 – 120°C  ±0.25°C       The  MPC  framework  for  ACMV  has  two  primary
                     Relative humidity  0 – 100%  ±1.5%        objectives: (i) minimizing the cooling power (Q ) consumed
                                                                                                   cool
                     Solar radiation  0 – 2000 W/m 2  ±10 W/m 2  by the ACMV system and (ii) maximizing thermal comfort
            Indoor   Air temperature  0 – 50°C  0.2°C          by maintaining the indoor PMV as close as possible to
            room space  Globe temperature  0 – 50°C  0.5°C     thermal neutrality (i.e., PMV  = 0). Feedback from room
                                                                                      ref
                     Relative humidity  0 – 100%  ±1.7%        air temperature, humidity, and globe temperature sensors is
                                                                                  33
                                   0 – 2000 ppm  ±30 ppm       used to determine PMV.  The objective function for ACMV
                     CO 2
            ACMV     BTU meter     0 – 50 kW  ±1%              is formulated as shown in Equation II:
            system   Elec. power meter  0 – 5 kW  ±0.5%                    N  W cool  * Q cool tk t |
                                                                                     ,
                     Duct air temperature 0 – 50°C  ±0.2°C     J   Minimize(   COP
                                                                           k0
                     Duct RH       0 – 100%   ±1.5%             N                      2  N         2

                                                                                             

                     Duct airflow  0 – 16 m/s  ±5% of the reading   W PMV  *( PMV t kt |   PMMV )   W *( tk t|  ) )  (II)
                                                                                    ref
                                                               k0                        k 0

                                   0 – 2000 ppm  ±30 ppm
                     Duct CO 2
            Abbreviations: ACMV: Air conditioning and mechanical ventilation;   This  objective  function  is  subject  to  the  following
            BTU: British thermal unit; RH: Relative humidity.  constraints, as expressed in Equations III–IV:
            Volume 2 Issue 1 (2025)                         43                             doi: 10.36922/ijamd.8161
   44   45   46   47   48   49   50   51   52   53   54